How To Size Your Motor
Back to Online Store
Spring Return Damper Actuators
Width (mm)and Height (mm)
250
500
750
1000
1250
1500
1750
2000
2250
2500
250 0.31NM
TF
0.63NM
TF
0.94NM
TF
1.25NM
TF
1.56NM
TF
1.88NM
TF
2.19NM
LF
2.50NM
LF
2.81NM
LF
3.12NM
LF
500 0.63NM
TF
1.25NM
TF
1.89NM
TF
2.50NM
LF
3.12NM
LF
3.75NM
LF
4.38NM
NF
5.00NM
NF
5.63NM
NF
6.25NM
NF
750 0.94NM
TF
1.88NM
TF
2.81NM
LF
3.75NM
LF
4.69NM
NF
5.63NM
NF
6.56NM
NF
7.50NM
AFR
8.44NM
AFR
9.38NM
AFR
1000 1.25NM
TF
2.50NM
LF
3.75NM
LF
5.00NM
LF
6.25NM
NF
7.50NM
AFR
8.75NM
AFR
10.00NM
AFR
11.25NM
AFR
12.50NM
AFR
1250 1.56NM
TF
3.13NM
LF
4.69NM
LF
6.25NM
NF
7.81NM
AFR
9.38NM
AFR
10.94NM
AFR
12.50NM
AFR
14.06NM
AFR
.
1500 1.88NM
TF
3.75NM
LF
5.63NM
NF
7.50NM
AFR
9.38NM
AFR
11.25NM
AFR
13.13NM
AFR
15.00NM
AFR
. .
1750 2.19NM
LF
4.38NM
NF
6.56NM
NF
8.75NM
AFR
10.94NM
AFR
13.13NM
AFR
. . . .
2000 2.50NM
LF
5.00NM
NF
7.50NM
AFR
10.00NM
AFR
12.50NM
AFR
15.00NM
AFR
. Note 1 . .
2250 2.81NM
LF
5.62NM
NF
8.44NM
AFR
11.25NM
AFR
14.06NM
AFR
. . . . .
2500 3.13NM
LF
6.25NM
NF
9.38NM
AFR
12.50NM
AFR
. . . . . .
Note 1: Larger Area Dampers Utilise Multiple Damper Actuators
Reference Table - Spring Return Damper Actuators
Actuator
Power Supply
Control Type
Torque (NM)
Approx. Max
Damper Size
TF230
TF24
TF24-SR
240V
24V
24V
On/Off
On/Off
0-10V Modulating
2
0.38m2
LF230
LF24
LF24-SR
240V
24V
24V
On/Off
On/Off
0-10V Modulating
4
0.75m2
NF230
NF24
NF24-SR
240V
24V
24V
On/Off
On/Off
0-10V Modulating
7
1.31m2
AFR230
AFR24
AFR24-SR
240V
24V
24V
On/Off
On/Off
0-10V Modulating
15
3.00m2
Non-Spring Return Damper Actuators
Width (mm) and Height (mm)
250
500
750
1000
1250
1500
1750
2000
2250
2500
250 0.31NM
CMU
0.63NM
CMU
0.94NM
CMU
1.25NM
CMU
1.56NM
CMU
1.88NM
CMU
2.19NM
LMU
2.50NM
LMU
2.81NM
LMU
3.13NM
LMU
500 0.63NM
CMU
1.25NM
CMU
1.88NM
CMU
2.50NM
LMU
3.13NM
LMU
3.75NM
LMU
4.38NM
LMU
5.00NM
LMU
5.63NM
NMU
6.25NM
NMU
750 0.94NM
CMU
1.88NM
CMU
2.81NM
LMU
3.75NM
LMU
4.69NM
LMU
5.63NM
NMU
6.56NM
NMU
7.50NM
NMU
8.44NM
NMU
9.38NM
NMU
1000 1.25NM
CMU
2.50NM
LMU
3.75NM
LMU
5.00NM
LMU
6.25NM
NMU
7.50NM
NMU
8.75NM
NMU
10.00NM
NMU
11.25NM
SMU
12.50NM
SMU
1250 1.56NM
CMU
3.13NM
LMU
4.69NM
LMU
6.25NM
NMU
7.81NM
NMU
9.38NM
NMU
10.94NM
SMU
12.50NM
SMU
14.06NM
SMU
15.63NM
SMU
1500 1.88NM
CMU
3.75NM
LMU
5.63NM
NMU
7.50NM
NMU
9.38NM
NMU
11.25NM
SMU
13.13NM
SMU
15.00NM
SMU
16.88NM
SMU
18.75NM
SMU
1750 2.19NM
LMU
4.38NM
LMU
6.56NM
NMU
8.75NM
NMU
10.94NM
SMU
13.13NM
SMU
15.31NM
SMU
17.50NM
SMU
19.69NM
SMU
21.88NM
GMU
2000 2.50NM
LMU
5.00NM
LMU
7.50NM
NMU
10.00NM
NMU
12.50NM
SMU
15.00NM
SMU
17.50NM
SMU
20.00NM
SMU
22.50NM
GMU
25.00NM
GMU
2250 2.81NM
LMU
5.63NM
NMU
8.44NM
NMU
11.25NM
SMU
14.06NM
SMU
16.88NM
SMU
19.69NM
SMU
22.50NM
GMU
25.31NM
GMU
28.13NM
GMU
2500 3.13NM
LMU
6.25NM
NMU
9.38NM
NMU
12.50NM
SMU
15.63NM
SMU
18.75NM
SMU
21.88NM
GMU
25.00NM
GMU
28.13NM
GMU
31.25NM
GMU
Reference Table - Non-Spring Return Damper Actuators
Actuator
Power Supply
Control Type
Torque (NM)
Approx. Max
Damper Size
CMU230
CMU24
CMU24-SR-R
240V
24V
24V
On/Off
On/Off
0-10V Modulating
2
0.38m2
LMU230
LMU24
LMU24-SR
240V
24V
24V
On/Off
On/Off
0-10V Modulating
5
1.00m2
NMU230
NMU24
NMU24-SR
240V
24V
24V
On/Off
On/Off
0-10V Modulating
10
2.00m2
SMU230
SMU24
SMU24-SR
240V
24V
24V
On/Off
On/Off
0-10V Modulating
20
4.00m2
GMU230
GMU24
GMU24-SR
240V
24V
24V
On/Off
On/Off
0-10V Modulating
40
8.00m2
Equation For Determining Damper Torque (NM)

Damper Torque = Damper Width x Damper Height x Force Generated By The Airflow


NB: In These Tables, The Force Generated By The Pressure And Velocity Of A Normal Air-conditioning System Is Approximately 5.00NM/m2.